LP40-33
GE Online-UPS Lanpro CE 40kVA, 3P-3P, Tower, S5
Technical Data Sheet LP33 10- 20 - 30 - 40kVA 400VAC CE S5
THÔNG TIN THAY THẾ ẮC QUY CHO UPS (UPS BATTERY REPLACEMENT) |
|||
Tên & số lượng bộ ắc quy lắp trong UPS (Internal battery cartridge name & quantity) |
|||
BỘ SẠC BÌNH (BATTERY CHARGER) |
480VDC ±240VDC/ Selectable: 1.4A, 2.8A, 4.2A (option up to 8.4A) Lấy trung tính (Split battery referenced to neutral/ Center tap) DC output voltage at 20°C Float: 2x 273 V Discharge end of battery 2x 198 VDC (1.65VPC) |
||
Bộ ắc quy lắp trong UPS (Internal battery pack) |
480VDC =±240VDC, lấy trung tính (Split battery referenced to neutral/ Center tap) =3x 2x 20x 12Vx 7Ah ~ 9Ah =3x 2x 1680VAh ~ 4x 2160VAh =120 bình, mắc thành 6 chuỗi 240VDC. |
||
Tủ ắc quy lắp ngoài/ Tủ ắc quy mở rộng (External battery cabinet/ External extended battery cabinet) |
480VDC =±240VDC, lấy trung tính (Split battery referenced to neutral/ Center tap) =3x 2x 20x 12Vx 7Ah ~ 9Ah =3x 2x 1680VAh ~ 4x 2160VAh =120 bình, mắc thành 6 chuỗi 240VDC. |
||
Thời gian sạc lại (Typical recharge time) |
6~8 giờ đạt 80%. 10+ giờ sạc đầy. Thời gian sạc có thể lâu hơn, phụ thuộc vào tổng dung lượng ắc quy được lắp đặt. |
||
Ắc quy khuyến nghị thay thế cho UPS (Recommended replacement battery) |
WP7.2-12 | WPL7.2-12 | |
WP7-12(28W | WP1236W | WP9-12SHR |